- Power Cables[305]
- Communication Cables[6]
- Electrical Wires[10]
- Other Wires[10]
- Control Cables[9]
- Contact Person : Mr. Chow Kelvin
- Company Name : Henan Tong-Da Cable Co., Ltd.
- Tel : 86-371-60311151
- Fax : 86-371-60311150
- Address : Henan,zhengzhou,No.299 Jinshui Road Pufa International Finance Center Mansion 1203 Room,Zhengzhou City Henan Province China Zhengzhou Branch
- Country/Region : China
- Zip : 450000
Grteased Conductor-ACSR Bare Conductor IEC61089
Application
The product is used in areas with bad weather conditions. It can be used in corrosive aeras like coastal areas industrial zones. This ACSR is filled with anti-corrosion grease applied on the gaps between stranded wires and their external surfaces.
Construction
Bare conductors with grease
Values of k are given in the following table for four cases of grease application, a grease density of 0.87 g/cm3, and a minimum fill factor of 0.70:
Case 1: Steel core only greased.
Case 2: All the conductor is greased except the outer layer.
Case 3: All the conductor is greased including the outer layer.
Case 4: All the conductor is greased except the outer surface of the wires in the outer layer.
Coefficient K for Mass of Grease
1089 IEC
Stranding | K1 | K2 | K3 | K4 | |
Aluminium | Steel | Case1 | Case 2 | Case3 | Case4 |
6 | 1 | - | - | 0.96 | 0.46 |
7 | - | - | - | 0.96 | 0.46 |
18 | 1 | - | 0.96 | 2.87 | 1.87 |
22 | 7 | 0.30 | 1.57 | 3.81 | 2.69 |
26 | 7 | 0.58 | 2.17 | 4.72 | 3.37 |
19 | - | - | 0.96 | 2.87 | 1.87 |
30 | 7 | 0.96 | 2.87 | 5.74 | 4.21 |
37 | - | - | 2.87 | 5.74 | 4.21 |
61 | - | - | 5.74 | 9.57 | 7.27 |
45 | 7 | 1.43 | 4.25 | 7.60 | 6.27 |
54 | 7 | 0.96 | 5.74 | 9.57 | 7.27 |
54 | 19 | 1.03 | 5.82 | 9.64 | 7.33 |
72 | 7 | 0.43 | 7.60 | 11.90 | 8.97 |
72 | 19 | 1.46 | 7.63 | 11.94 | 9.42 |
84 | 7 | 0.96 | 9.57 | 14.35 | 11.11 |
84 | 19 | 1.03 | 9.64 | 14.43 | 11.18 |
91 | - | - | 9.57 | 14.35 | 11.11 |
Grteased Conductor-ACSR Bare Conductor IEC61089